Page -1-! WARNING - SHOCK HAZARD! DANGER SERVICE MANUAL12VDC WALL THERMOSTATAIR CONDITIONINGSYSTEMS ROOFTOP UNITS ONLYTO PREVE
Page -10-Anytime the thermostat is placed in the HIGH COOL position you should be able to read12VDC between terminals GH and B for the High Fan, and
Page -11-Figure 7. High Voltage 9-Pin ConnectorNote: To check voltage at the 9 pin connector plug it may be necessary to unplug the upper unit fromthe
Page -12-
Page -13-
Page -14-
Page -15-
Page -16-VI.WIRING DIAGRAMS 7330-730 & 8330-733 Series Cool Only Ducted Ceiling Plenums7330-735, 7330-736 & 8330-735 Series Heat/ Cool Ducted
Page -17-7330-720 & 8330-723 Series Cool Only Remote Free Delivery Ceiling Plenums7330-725, 7330-726 & 8330-725 Series Heat/Cool Remote Free D
Page -18-RV ProductsA Division of Airxcel, Inc.P.O. Box 4020Wichita, KS 672041976-376 (4-02)
Page -2-TABLE OF CONTENTS PAGEI. INTRODUCTION TO WALL THERMOSTATS ... 3II INTRODUCTION TO RELAYS ...
Page -3-I.INTRODUCTION TO WALL THERMOSTATSAll of the air conditioning functions are controlled by the wall mounted thermostat . Thesethermostats utili
Page -4-The following chart shows the different electrical connections made by the thermostat duringoperation. The chart below assumes12VDC(+) is supp
Page -5-THERMOSTAT LOCATIONThermostats are very sensitive instruments. For accurate temperature control and comfort thefollowing considerations for th
Page -6-Figure 1III.CEILING PLENUMS WITH INDIVIDUAL RELAYSRecreational Vehicle Products built 2 types of ceiling assembly packages which incorporate i
Page -7-Figure 3The following charts depict the thermostat control wiring, ceiling assembly wiring destinations, andrelay functions for air conditione
Page -8-furnace control circuit, (Usually a time delay relay located at the furnace).IV.CEILING PLENUMS WITH PRINTED CIRCUIT BOARDSMost of the 7000 an
Page -9-Note: In ducted applications similar to the one found in Figure 4, the Printed Circuit Board /Control Box Assembly is found mounted in the re